Error Code 7113/7116/7117 - Mitsubishi Electric PUHY-RP200 Service Handbook

Hide thumbs Also See for PUHY-RP200:
Table of Contents

Advertisement

[ IX Troubleshooting ]
1. Error Code
7113
Function setting error
2. Error source, cause, check method and remedy
Error source
Outdoor unit
(1)
(2)
(3)
1. Error Code
7116
REPLACE unit cleaning setting error
Refrigerant pipe cleaning has not been completed.
2. Error source, cause, check method and remedy
Error source
Outdoor unit
1. Error Code
7117
Model setting error
2. Error source, cause, check method and remedy
Error source
Outdoor unit
(1)
(2)
HWE10130
Cause
Wiring failure
Disconnected connector, short cir-
cuit, contact failure
Incompatibility between the control
board and INV board (Replacement
of the circuit board with the wrong
one)
Cause
Refrigerant pipe cleaning has not been com-
pleted.
The model setting switch (SW4-7) is set incor-
rectly.
Cause
Wiring failure
Disconnected connector, short circuit, contact
failure
Check method and remedy
1)
Control board connector
Check the CNTYP2,4,5 connector connection.
INV board connector
Check the CNTYP connector connection
2)
Check the compatibility of the circuit board, and replace
it with a correct one if necessary.
3)
Check the model selection switch on the outdoor unit
(Dipswitch SW5-7 on the control board.).
Check method and remedy
Check the setting for SW4-7 on the control
board.
Check method and remedy
1)
Control board connector
Check the CNTYP2,4,5 connector connec-
tion.
INV board connection
Check the CNTYP connector connection