Model 4720 Terminal Strip Description - Regency 4720 Installation Manual

Control/communicator
Table of Contents

Advertisement

Regency
®
Model 4720 Control/Communicator Installation Manual (P/N 150476, Rev. A)

Model 4720 Terminal Strip Description

3.14
Terminal #
1
AC input
2
AC input
3
Earth Ground
4
Siren Power
5
Auxiliary (Bell) Power
6
Circuit Ground
7
External Speaker/Bell Output (Active Low)
8
Internal (Touchpad) Speaker Output (Active Low)
9
Circuit Ground
10
Smoke Detector Power
11
Loop Power
12
Loop Power
13
Loop Power
14
Loop Power
15
Optional output for use with Model 4724 Control
Expander
16
Model 4203 Touchpad Pin 1
17
Model 4203 Touchpad Pin 2
18
Model 4203 Touchpad Pin 3
19
Touchpad Ground
20
Touchpad Power
21
Data Output to Touchpad
22
Data Input From Touchpad
23
Zone 1 Input
24
Zone 2 Input
25
Zone 3 Input
26
Zone 4 Input
27
Zone 5 Input
28
Zone 6 Input
29
Zone 7 Input
30
Zone 8 Input
31
Zone 9 Input
32
Zone 10 Input
33
Zone 11 Input
34
Zone 12 Input
35
Zone 13 Input
36
Zone 14 Input
37
Zone 15 Input
38
Zone 16 Input/Mechanical Key Input
39
Ground Start Output 100 mA Max. Active Low
40
Dialer Failed Output 100 mA Max. Active Low
41
Telco Tip
42
Telco Ring
43
House Tip
44
House Ring
45
Audio Output (Alarm and Alert Tones)(Active Low)
* Note 1: Terminal 4 (16 V) will be at 20 V under normal standby conditions (non-alarm).
* Note 2: Each device connected to Terminal 5 or 10 must be rated for the voltage ranges specified. The minimum
voltage occurs when AC power is off and the battery is discharging under load. The maximum voltage
occurs when AC power is on and the output is not loaded.
* Note 3: The total current drain of Terminal 5, Terminal 10, all touchpads, and all XBUS expansion devices, must
not exceed 1.35 A (see Table 4.1.1.0a).
* Note 4: See Section 3.3.1 for an explanation of PolySwitch protection.
UL note: Refer to wiring diagram on the unit for ratings/connections.
Terminal Description
16
Electrical Ratings
16.5 V
, 60 Hz, 40 VA
AC
16.5 V
, 60 Hz, 40 VA
AC
16 V
unregulated (1-A load) max.
DC
10.2 V
- 13.7 V
, 1 A max.
DC
DC
(PolySwitch-protected to 1.1 A min. -
Revision L and later PCB revs.)
1.5 A - earlier revisions)
500 mA max.
11.2 V
- 14 V
, 150 mA max. *2 *3
DC
DC
+12 V
, 50 mA max. (current limited)
DC
+12 V
, 50 mA max. (current limited)
DC
+12 V
, 50 mA max. (current limited)
DC
+12 V
, 50 mA max. (current limited)
DC
Revised 10/98
*1
*2 *3
*4