Vent Requirements - Jøtul GF 400 BV Sebago Installation And Operation Instructions Manual

Direct vent gas stove
Table of Contents

Advertisement

Approved B-Vent Configurations
Maximum
chimney
height off
Draft Hood is
35 feet.
Minimum
chimney
height off
Draft Hood is
7 feet.
Figure 7.
Listed B-Vent
termination
cap required.
chimney height
from Draft Hood
Maximum
horizontal
offset
anywhere in
venting
configuration
is 4 feet.
Figure 9.
10
Listed B-Vent
Termination Cap
required.
NOTE:
Installation at
altitude greater
than 2000'
requires
minimum 12 ft.
vertical rise
from Draft
Hood.
NOTE:
Installation at
altitude greater
than 2000'
requires
Minimum
minimum 12 ft.
vertical rise
from Draft
is 7 feet.
Hood.
Listed B-Vent
Termination
Maximum
total horizontal
anywhere in
configuration
Minimum
chimney height
from Draft
Hood is 7 feet.
Figure 8.
Listed B-Vent
termination cap
required.
Maximum
total horizontal
offset
anywhere in
venting
configuration
Minimum
is 4 feet.
chimney height
from Draft
Hood is 7 feet.
Figure 10.
Cap
NOTE:
required.
Installation at
altitude greater
than 2000'
requires
venting
minimum 12 ft.
vertical rise
is 4 feet.
from Draft
Hood.
Max. Four, 45°
or Three, 90°
Elbows
NOTE:
Installation at
altitude greater
than 2000'
requires
minimum 12 ft.
vertical rise
from Draft
Hood.
Max. Four, 45°
or Three, 90°
Elbows