23a
Room temperature influence -
line 3
This section is only relevant if you have installed a room sensor or
ECA 60 / ECA 61 / ECA 62 / ECA 63.
3
Min.
0
influence
3
Room temperature influence
Circuit
I / (II)
The bar below the min. value blinks. Adjust the
min. influence.
Select the max. influence.
The bar below the max. value blinks.
Adjust the max. influence.
There are two basic principles for control of the room
temperature influence:
A: Max. room temperature limitation
Use this limitation if your heating system is fully equipped
with radiator thermostats and you also want to obtain a max.
limitation of the room temperature. The controller will allow
for free heat gains, i.e. solar radiation or heat from a fire place,
etc.
Influence
The max. influence determines how much the room
temperature should influence the desired flow temperature.
Example
The actual room temperature is 2 degrees too high.
The influence at max. limitation (right corner of the display) is
set to -40.
The influence at min. limitation (left corner of the display) is set
to 0.
Heat curve H is 1.8.
Result:
The desired flow temperature is changed by
2 x -40 x 1.8 x 0.1 = -14.4 degrees.
The grey
side of the
ECL Card
1
1
2
ON
ON
Setting range
0 ... 99 / -99 ... 0
Desired room
temperature
Max.
limitation
3
ON
Max.
-4
0
influence
min. 0 / (0) max. -40 / (-40)
Factory setting
Room
temperature