Danfoss C67 User Manual page 49

Ecl comfort
Table of Contents

Advertisement

Service parameter(s) 14-15
14 Optimizing time constant
Circuit
(I) / (II)
Optimizes the start and stop times for the comfort temperature
period to obtain the best comfort at the lowest energy
consumption. The lower the outdoor temperature, the earlier the
heating cut-in.
Adjust the optimizing time constant. The value
consists of a two digit number.
The two digits have the following meaning:
Digit 1
Digit 2
OFF: No optimization. The heating starts and
Dimensioning temperature:
The lowest outdoor temperature (usually determined by your
system designer in connection with the design of the heating
system) at which the heating system can maintain the designed
room temperature.
15 Adaptive function of room temperature
Circuit
(I) / (II)
Controls how fast the room temperature adapts to the desired
room temperature.
The adaptive funtion will eliminate the difference
between the desired and the actual room
temperature. This is done by integrating the
difference and adjusting the desired flow
temperature.
OFF: The adaptive funtion is cancelled.
1:
30:
Setting range
OFF / 10 ... 59
Heat accumulation of
the building
1
medium
2
3
medium
4
5
Dimensioning
temperature
0
1
5
9
stops at the times set in the schedule.
Setting range
OFF / 1 ... 30
The desired temperature is adapted quickly.
The desired temperature is adapted slowly.
light
heavy
heavy
- 50 °C
- 45 °C
- 25 °C
- 5 °C
32c
Factory setting
(OFF) / (OFF)
System type
Radiator
systems
Floor heating
systems
Capacity
large
normal
small
Factory setting
(OFF) / (OFF)
The grey
side of the
ECL Card

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents