Installation Instructions Please note This product should only be installed by a suitably qualifi ed electrician or heating installer. The installation must comply with local Building Regulations and Wiring Regulations, including any competent person requirements that may exist. Specifi cation Thermostat features Temperature Range 10-30°C...
Installation First remove the wallplate from the back of the unit. Fix at a height of approximately 1.5m from the fl oor, away from draughts or heat sources such as fan-coil outlets, sunlight or offi ce equipment. Wiring Connection Diagram Electronics Cool Heat return...
Page 5
DIL Switch options, shown in factory set position. Sw On Fan Con Fan Auto DIL Switch Descriptions Switch 1: Not used on this model Switch 2: MOT - Motorised valve actuator selection. WAX - Wax valve actuator selection. Mounting thermostat to the wallplate To mount the thermostat to the wallplate, align the tabs on the top of the thermostat with the apertures in the wallplate and hinge the thermostat down, pressing fi rmly to engage...
Locking & limiting To lock or limit the setting range turn the setting dial to 3 and remove knob. Position the locking springs on the rear of the dial to the desired position and re-mount the knob ensuring that number 3 on the dial aligns with the reference mark on the case.
Page 8
www.danfoss.com/BusinessAreas/Heating (2004/108/EC) (2006/95/EC) Part No 25284v01 07/08...