Danfoss C67 User Manual page 48

Ecl comfort
Table of Contents

Advertisement

32b
Service parameter(s) 13
13 Reference ramping
Circuit
(I) / (II)
The time in which the desired flow temperature increases slowly
to avoid load peaks in the heat supply.
Set the ramping time for the controller.
Temperature °C
In order to avoid load peaks in the supply network, the flow
temperature can be set to increase slowly after a period with
setback temperature. This causes the valve to open slowly.
The grey
side of the
ECL Card
Setting range
0 ... 99 min.
Setting line 13
Factory setting
(0) / (0) min.
Time (min.)