Change To Room Control Only; Extending Maximum Oor Temperature Limitation To 45°C - Danfoss ECtemp Next Plus Installation Manual

Electronic intelligent timer thermostat
Hide thumbs Also See for ECtemp Next Plus:
Table of Contents

Advertisement

Danfoss ECtemp Next Plus
Press any other button to exit or wait for automatic exit
after 6 sec. without operation
4.9

Change to Room control only

Switch Power OFF
Press M and Timer buttons simultaneously for approx. 10
seconds
Select Function P08: Only Room temperature control
Select Setting 01:
Switch Power ON
Press M button for approx. 6 seconds
Select Parameter Setting P02:
Select Setting Range 03:
4.10 Extending Maximum oor temperature limita-
tion to 45°C
Power OFF
Press M and Timer buttons simultaneously for 10 seconds
into those parameters setting.
Select Function P07 (Table in 4.11): Setting range extension
Select Setting 02:
Adjust Maximum Floor temperature according to need up
to 45°C
Power ON
Installation Guide
Enable
Temperature Control mode
Room Only mode
for P06, P07 and P08
Maximum 45°C
15