Danfoss C67 User Manual page 47

Ecl comfort
Table of Contents

Advertisement

Service parameter(s) 10-11
10 Choice of room panel / remote control
Circuit
I / (II)
Decides the communication with the room panel or remote
control.
Please note that the room panel / remote control is only active
if the system device bus is active. The bus is active when the
outdoor temperature sensor is connected.
Choose between
0:
1:
2:
3 ... 5: Not used
The room panel / remote control has no influence on the DHW
control.
11 Setback temperature dependent on outdoor
temperature
Circuit
(I) / (II)
Below this outdoor temperature, the setback temperature setting
has no influence.
-29 ... 10:
OFF: The setback temperature does not depend
Reduction
100%
0%
Setting range
Not to be used
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address A
Room panel ECA 60 / 62 or remote control
ECA 61 / 63 with address B
Setting range
OFF / -29 ... 10 °C
The setback temperature depends on the
outdoor temperature, when the outdoor
temperature is above the set limit. The
lower the outdoor temperature, the less the
temperature reduction. When the outdoor
temperature is below the set limit, there is
no temperature reduction.
on the outdoor temperature.
-29
-20
-10
Setting line 11
0 ... 5
0
10
20
32a
Factory setting
5 / (5)
Factory setting
(-15) / (-15) °C
Outdoor
temperature °C
The grey
side of the
ECL Card

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents