Safety Considerations - Carrier AQUAFORCE 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Hide thumbs Also See for AQUAFORCE 30XA080-500:
Table of Contents

Advertisement

CONTENTS (cont)
SERVICE . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 74-87
Economizer Assembly. . . . . . . . . . . . . . . . . . . . . . . . . . . 74
Electronic Expansion Valve (EXV) . . . . . . . . . . . . . . . 74
• DX COOLER MAIN EXV CONTROL
• EXV TROUBLESHOOTING PROCEDURE
Compressor Assembly . . . . . . . . . . . . . . . . . . . . . . . . . . 77
• COMPRESSOR OIL SYSTEM
Flooded Cooler Units. . . . . . . . . . . . . . . . . . . . . . . . . . . . 79
• FLOODED COOLER SUCTION SERVICE VALVE
• FLOODED COOLER LOSS OF FLUID FLOW
PROTECTION
• FLOODED COOLER TUBE PLUGGING
• FLOODED COOLER RETUBING
DX Cooler Units . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 82
• DX COOLER SUCTION SERVICE VALVE
• DX COOLER FREEZE PROTECTION
• DX COOLER LIQUID FLUID TEMPERATURE
• DX COOLER TUBE PLUGGING
• DX COOLER RETUBING
DX Cooler and Flooded Cooler Units . . . . . . . . . . . . 84
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
RTPF Condenser Coil Maintenance and Cleaning
Recommendations . . . . . . . . . . . . . . . . . . . . . . . . . . . . 85
• REMOVE SURFACE LOADED FIBERS
• PERIODIC CLEAN WATER RINSE
Condenser Fans. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
Refrigerant Circuit. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 86
• LEAK TESTING
• REFRIGERANT CHARGE
Safety Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
Relief Devices . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87
• PRESSURE RELIEF VALVES
MAINTENANCE. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 87,88
Recommended Maintenance Schedule . . . . . . . . . . 87
TROUBLESHOOTING. . . . . . . . . . . . . . . . . . . . . . . . 88-109
Alarms and Alerts . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 88
Service Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 104
DISPLAY TABLES . . . . . . . . . . . . . . . . . . . . . . . . . 110-127
DISPLAY TABLES. . . . . . . . . . . . . . . . . . . . . . . . . . 128-141
APPENDIX C - CCN TABLES . . . . . . . . . . . . . . 142-156
DIP SWITCH ADDRESSES. . . . . . . . . . . . . . . . 157-160
INSTRUMENTATION . . . . . . . . . . . . . . . . . . . . . . 161-164
612
Page
AND LOG SHEETS. . . . . . . . . . . . . . . . . . . . . . . . . . 165-167
APPENDIX G - BACNET COMMUNICATONS
OPTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 168-178
INDEX . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 179
START-UP CHECKLIST
FOR 30XA LIQUID CHILLERS . . . . . . . . CL-1 to CL-8

SAFETY CONSIDERATIONS

Installing, starting up, and servicing this equipment can be
hazardous due to system pressures, electrical components, and
equipment location (roof, elevated structures, etc.). Only
trained, qualified installers and service technicians should
install, start up, and service this equipment. When working on
this equipment, observe precautions in the literature, on tags,
stickers, and labels attached to the equipment, and any other
safety precautions that apply. Follow all safety codes. Wear
safety glasses and work gloves. Use care in handling, rigging,
and setting this equipment, and in handling all electrical
components.
Electrical shock can cause personal injury and death. Shut
off all power to this equipment during installation and ser-
vice. There may be more than one disconnect switch. Tag
all disconnect locations to alert others not to restore power
until work is completed.
DO NOT VENT refrigerant relief valves within a building.
Outlet from relief valves must be vented in accordance
with the latest edition of ANSI/ASHRAE (American
National Standards Institute/American Society of Heating,
Refrigerating and Air Conditioning Engineers) 15 (Safety
Code for Mechanical Refrigeration). The accumulation of
refrigerant in an enclosed space can displace oxygen and
cause asphyxiation. Provide adequate ventilation in
enclosed or low overhead areas. Inhalation of high concen-
trations of vapor is harmful and may cause heart irregulari-
ties, unconsciousness or death. Misuse can be fatal. Vapor
is heavier than air and reduces the amount of oxygen avail-
able for breathing. Product causes eye and skin irritation.
Decomposition products are hazardous.
DO NOT USE TORCH to remove any component. System
contains oil and refrigerant under pressure.
To remove a component, wear protective gloves and gog-
gles and proceed as follows:
a. Shut off electrical power to unit.
b. Recover refrigerant to relieve all pressure from sys-
tem using both high-pressure and low pressure ports.
c. Traces of vapor should be displaced with nitrogen
and the work area should be well ventilated. Refrig-
erant in contact with an open flame produces toxic
gases.
d. Cut component connection tubing with tubing cutter
and remove component from unit. Use a pan to catch
any oil that may come out of the lines and as a gage
for how much oil to add to the system.
e. Carefully unsweat remaining tubing stubs when nec-
essary. Oil can ignite when exposed to torch flame.
Failure to follow these procedures may result in personal
injury or death.