Dual Chiller Pump Control For Series Chiller Applications Night Time/Low Noise Applications - Carrier AQUAFORCE 30XA080-500 Controls, Start-Up, Operation, Service And Troubleshooting Instructions

Air-cooled liquid chillers
Hide thumbs Also See for AQUAFORCE 30XA080-500:
Table of Contents

Advertisement

Table 34 — Dual Slave Chiller Control Parameters for Series Applications with Touch Pilot Display
DISPLAY NAME
Master/Slave Select
Master Control Type
Slave Address
Lead Lag Select
Lead/Lag Balance Delta
Lag Start Timer
Lead Pulldown Time
Start If Error Higher
Lag Minimum Running Time
Lag Unit Pump Control
Chiller In Series
NOTE: If pump control is configured to OFF, then LAG UNIT PUMP
SELECT = 1. If pump control is set to any other value, then LAG
Table 35 — Dual Slave Chiller Control Parameters for Series Applications with Navigator Display
ITEM
ITEM EXPANSION
MSSL
Master/Slave Select
SLVA
Slave Address
LLBL
Master Lead Lag Select
LLBD
Lead/Lag Balance Delta
LLDY
Lag Start Delay
LL.ER
Start If Error Higher
LAG.M
Lag Unit Pump Select
LPUL
Lead Pulldown Time
SERI
Chillers in Series
OPER
Operating Control Type
NOTE: If pump control is configured to OFF, then LAG UNIT PUMP
SELECT = 1. If pump control is set to any other value, then LAG
UNIT PUMP SELECT = 0. This configuration must be set consis-
tently for both master and slave chillers.
DUAL CHILLER PUMP CONTROL FOR SERIES
CHILLER APPLICATIONS — Pump control for series chill-
er applications is controlled by the master chiller only. The
control of the slave chiller is directed through commands emit-
ted by the master chiller. The slave chiller has no action in
master/slave operations. The slave chiller only verifies that
CCN communication with the master chiller is present. See the
Dual Chiller Sequence of Operation section on page 68.
PATH
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
Main Menu
Config
MST_SLV
PATH
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Configuration
RSET
Operating Modes
SLCT
LINE NO.
2 (Slave)
3
Default: 0 (Disable)
1 (Local Control)
2 (Remote Control)
7
3 (CCN Control)
Default: 1 (Local Control)
Value: Configure for proper control type.
Must be set to the Slave Chiller's address.
The master and slave chiller must have
11
different addresses and be on the same
Bus Number
Default: 2
0 (Master Always Leads)
1 (Lag Once Failed Only)
12
2 (Lead/Lag Runtime Select)
Default: 0 (Master Always Leads)
Range: 40 to 400 hours
16
Default: 168 hours
Range: 2 to 30 minutes
17
Default: 10 minutes
Range: 0 to 60 minutes
18
Default: 0 minutes
Range: 3.0 to 18 F (1.7 to 10.0 C)
19
Default: 4.0 F (2.2 C)
Range: 0 to 150 minutes
20
Default: 0 minutes
0 (Stop If Unit Stops)
21
1 (Run If Unit Stops)
Default: 0 (Stop If Unit Stops)
Yes
22
Default: No
UNIT PUMP SELECT = 0. This configuration must be set consis-
tently for both master and slave chillers.
Slave
Default: Disable
Must be set to the Slave Chiller's address.
The master and slave chiller must have
different addresses and be on the same
Bus Number
Default: 2
Range: Always Lead, Lag if Fail,
Runtime Sel
Default: Always Lead
Range: 40 to 400 hours
Default: 168 hours
Range: 2 to 30 minutes
Default: 10 minutes
Range: 3.0 to 18 F (1.7 to 10.0 C)
Default: 4.0 F (2.2 C)
Range: Off If U Stp, On If U Stop
Default: Off If U Stp
Range: 0 to 60 minutes
Default: 0 minutes
YES
Default: NO
CCN Control
Night Time/Low Noise Operation —
fortLink™ controls have the ability to lower the sound level of
the machine by reducing the number of fans that are running,
provided that the conditions are acceptable. Reducing the num-
ber of running fans also limits the capacity. Three parameters
must be configured for this operation. A start and end time for
the mode of operation is required and an optional capacity limit
set point must also be configured.
37
VALUE
VALUE
The Com-