INSTALLATION
Model VMP-WModel
Model VMP-W
Burner Motor **
HP
Wa s
Approximate Weights
Shipping Weight
LB
KG
Opera ng Weight
LB
KG
Approximate Fuel Consump on at Rated Capacity+
Natural Gas
3
FT
M
3
Required Gas Pressure (IN. W.C./PSIG)
Minimum/Maximum
208V, 60 CY, 3 Phase
230V 60 CY 3 Phase
460V 60 CY 3 Phase
Specifi ca ons and dimensions are approximate. We reserve the right to change data without prior no fi ca on.
Design condi ons based on 160 F return and 180 F supply.
+ Consump on based on natural gas 1000 Btu/ 3.
** Sub 20 ppm; for lower requirements, consult factory.
3. See Table 3 for minimum make up air openings required
for each model.
TABLE 3 MINIMUM MAKE UP AIR OPENING REQUIREMENTS
Model
Fresh Air Opening FT2 (M2)
40
50
60
80
100
130
150
4. If positive forced ventilation is adopted, ensure that
there will be no appreciable pressure variation in the
equipment room.
5. Avoid ventilation which creates a negative pressure
in the building as it will seriously a ect combustion
and proper operation of the burner. Please note that
exhaust fans or similar equipment can create a down
draft in the chimney or starve the burner's air supply.
Either case may result in poor combustion or nuisance
failures. A properly designed make-up air system in the
equipment room will preclude these possibilities and is
2-6
Model VMP-W Low Emissions (LE) MOTOR
40
40
5
3730
6575
2982
8659
3928
1595
45
30/10
16.7
15.2
7.6
1 (.09)
1 (.09)
1.5 (.14)
4 (.37)
4 (.37)
5 (.46)
7.5 (.69)
VMPW-IOM-2012-1001
50
60
80
50
60
80
5
5
5
3730
3730
3730
7373
8170
8800
3345
3706
3992
9684
10671
12051
4393
4840
5466
1992
2392
3188
56
68
90
30/10
40/10
40/10
16.7
16.7
16.7
15.2
15.2
15.2
7.6
7.6
7.6
required to maintain proper combustion.
6. Eliminate potential for high risk situations for particulate
matter to be in the combustion air supply (e.g., as a
result of construction and maintenance activities).

Utilities

The Gas Supply

Adhere to the following for gas supply installation:
1. Install gas piping in accordance with all applicable
codes.
2. Ensure pipe and ttings used are new and free of dirt or
other deposits.
3. Ensure piping is of the proper size for adequate gas
supply to the gas head assembly. Consult your gas
company for speci c recommendations.
4. When making gas piping joints, use a sealing
compound resistant to the action of lique ed
petroleum gases. Do not use Te on tape on gas line
heads.
SECTION 2
100
130
150
100
130
150
5
Consult
Consult
3730
Factory
Factory
10300
12800
12800
4672
5806
5806
14700
20585
20585
6668
9337
9337
3985
5182
5978
113
147
169
40/10
60/10
60/10
24.2
Consult Factory
22
Consult Factory
11
Consult Factory