Carrier 40UV Installation, Start-Up And Service Instructions Manual page 19

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

UNIT
HP
40UH200
3
/
4
(at 2000 Cfm)
LEGEND
DX
— Direct Expansion
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
— Permanent Split Capacitor
*Left hand coil connections only.
Table 3 — Electric Heater Data for Units with ECM (cont)
NUMBER
NOMINAL
OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6*
3
4
240/1/60
5*
6
3
4
277/1/60
5
6
3
4
208/3/60
5
6
3
4
240/3/60
5
6
3
4
460/3/60
5
6
LAT
FLA
(F)
50.1
84
64.6
89
79.0
94
93.5
99
56.8
89
73.5
96
90.1
102
48.8
89
63.3
96
77.7
102
31.8
84
46.3
89
56.9
94
56.9
99
35.7
89
52.4
96
64.6
102
64.6
108
16.9
89
25.2
96
31.3
102
31.3
108
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
19
MCA
MOCP
CAPACITY
62.7
70
80.7
90
98.8
100
116.8
125
71.0
80
91.8
100
112.7
125
61.0
70
79.1
80
97.1
100
39.8
40
57.9
60
71.1
80
71.1
80
44.6
45
65.5
70
80.8
90
80.8
90
21.1
25
31.5
35
39.1
40
39.1
40
TOTAL
(kW)
9.0
12.0
15.0
18.0
12.0
16.0
20.0
12.0
16.0
20.0
9.0
12.0
15.0
18.0
12.0
16.0
20.0
24.0
12.0
16.0
20.0
24.0