Carrier 40UV Installation, Start-Up And Service Instructions Manual page 17

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

UNIT
HP
40UV,UH125
1
/
2
(at 1250 Cfm)
LEGEND
DX
— Direct Expansion
FLA
— Full Load Amps
LAT
— Leaving-Air Temperature at 70 F Entering-Air
Temperature
MCA
— Unit Minimum Circuit Ampacity
MOCP — Maximum Overcurrent Protection (Maximum Fuse Size
or Circuit Breaker Amps)
PSC
— Permanent Split Capacitor
*Left hand coil connections only.
Table 3 — Electric Heater Data for Units with ECM (cont)
NUMBER
NOMINAL
OF
V/Ph/Hz
ELEMENTS
3
4
208/1/60
5
6
3
4
240/1/60
5
6*
3
4
277/1/60
5
6
3
4
208/3/60
5
6
3
4
240/3/60
5
6
3
4
460/3/60
5
6
LAT
FLA
(F)
39.4
89
51.5
96
63.5
102
75.5
108
45.0
96
58.9
104
72.7
113
86.6
121
39.0
96
51.0
104
63.1
113
75.1
121
24.2
89
36.2
96
45.0
102
45.0
108
27.4
96
41.3
104
51.5
113
51.5
121
13.2
96
20.2
104
25.3
113
25.3
121
NOTES:
1. LAT (Leaving Air Temperature) (F) is measured at nominal cfm.
2. Water and DX coil used on electric heat units have left-hand
coil connections.
3. Electric heat is available in the reheat position only and connec-
tions are on the right side.
4. Face and bypass units are available with 3 heating elements
only.
17
MCA
MOCP
CAPACITY
49.3
50
64.3
70
79.4
80
94.4
100
56.2
60
73.6
80
90.9
100
108.3
110
48.7
50
63.8
70
78.8
80
93.9
100
30.2
35
45.3
50
56.3
60
56.3
60
34.2
35
51.6
60
64.3
70
64.3
70
16.5
20
25.2
30
31.6
35
31.6
35
TOTAL
(kW)
7.5
10.0
12.5
15.0
10.0
13.3
16.7
20.0
10.0
13.3
16.7
20.0
7.5
10.0
12.5
15.0
10.0
13.3
16.7
20.0
10.0
13.3
16.7
20.0