Unit Ventilator Comfort Control Module; Installation And Field Wiring - Carrier 40UV Installation, Start-Up And Service Instructions Manual

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

CONTROL BOARD
TERMINAL
T1
Space Temperature (+)
T2
Space Temperature (Gnd)
T3
Supply-Air Temperature (+)
T4
Supply-Air Temperature (Gnd)
T5
Mixed-Air Temperature (+)
T6
Mixed-Air Temperature (Gnd)
T7
Outdoor-Air Temperature (+)
T8
Outdoor-Air Temperature (Gnd)
T9
Space Temperature Adjust (+)
T10
Space Temperature Adjust (Gnd)
T11
Not Used
T12
Not Used
T13
Air Quality (+)
T14
Air Quality (Gnd)
T15
Relative Humidity (+)
T16
Relative Humidity (Gnd)
T17
Fan Status
T18
Not Used
T19
Outdoor Air Enthalpy
T20
Remote Start/Stop
ON
OF F
MAX
HI
LOW
Fig. 10 — Control Switch Location
Table 10 — Control Board Terminal Designations
FUNCTION
27
CONTROL BOARD
TERMINAL
T21
Fire/Smoke Status
T22
Freezestat
T23
Changeover
T24
Spare
T25
Common/Ground
T26
24 VDC (External Power Supply)
T27
Not Available
T28
Cooling First Stage or Valve Open
T29
Cooling Common
T30
Cooling Second Stage or Valve Close
T31
Heating First Stage or Valve Open
T32
Heating Common
T33
Heating Second Stage or Valve Close
T34
OAD Open
T35
OAD Common
T36
OAD Close
T37
Heating Enable
T38
Common
T39
Cooling Enable
LEGEND
Gnd — Ground
OAD — Outdoor-Air Damper
Unit Ventilator Comfort Control Module Instal-
lation and Field Wiring —
installed and factory-wired within the control compartment.
The Unit Ventilator Comfort Control module contains the soft-
ware and microprocessor that operates the unit. It continuously
monitors inputs and controls outputs such as the fan cooling
and heating coil valves and dampers. Refer to Fig. 11 for
wiring diagram connections between the unit's sensors and
actuators and the control module. Direct expansion cooling
and/or electric heat stage control are also provided.
FUNCTION
The module is factory-

Hide quick links: