Carrier 40UV Installation, Start-Up And Service Instructions Manual page 48

Unit ventilators with product integrated control (pic)
Table of Contents

Advertisement

DESCRIPTION
Alarm Routing Control
Realarm Time
Cntrl Temp Hys
Supply Air Temperature
Lo Lim
Hi Lim
Mixed Air Temperature
Lo Lim
Hi Lim
Relative Humidity
Lo Lim
Hi Lim
Outdoor Air CFM
Lo Lim
Hi Lim
Air Quality
Lo Lim
Hi Lim
Outdoor Air Temperature
Lo Lim
Hi Lim
*0 = Disable
1 = Enable.
†255 disables realarming.
DESCRIPTION
Desired Mode
Equipment Status
Controlling Temperature
Space Temperature
Supply Air Temperature
Mixed Air Temperature
Outdoor-Air Temperature
Fan Relay
Fan Status
Remote Start
Outdoor Air Enthalpy
Cooling Capacity
Heating Capacity
Outdoor Air cfm
MAD Capacity 0.0 - 100.0
Filter Status
Air Quality (PPM)
Relative Humidity
Fire Shutdown
FS
Coil Freeze Detection
Changeover Switch Input
Spare Discrete Input
Spare Analog Input
Mixed Air Damper 1
Mixed Air Damper 2
Cooling 1
Cooling 2
Heating 1
Heating 2
Heating Enable Output
Cooling Enable Output
*The text used for Mode shall be one of the following:
Off, Occ Cool, Occ Heat, Fan Only, UnocCool, UnocHeat, Warm-Up, Free Cool.
†The text used for Fan Status shall be one of the following:
Off, Low, Medium, High.
**0 = Off, High, or Clean
1 = On, Low, or Dirty.
NOTE: The presence of override limits indicates that the point is forcible, all others are read
only.
Table 25 — Alarm Service Configuration
POINT NAME
STATUS / UNITS
ALRMCNT
xxxxxxxx
REALARM
xxx
xx.x
SPTHYS
LOWLIM
xxx.x
HIGHLIM
xxx.x
LOWLIM
xxx.x
HIGHLIM
xxx.x
LOWLIM
xxx.x
HIGHLIM
xxx.x
LOWLIM
xxxx.x
HIGHLIM
xxxx.x
LOWLIM
xxxx.x
HIGHLIM
xxxx.x
LOWLIM
xxx.x
HIGHLIM
xxx.x
Table 26 — Status Display
POINT NAME
MODE
ALARM
SPT
RAT
SAT
MAT
OATEMP
SF
FANSTAT
REMOTE
ENT
CCAP
HCAP
OACFM
MIXDCAP
FLTSTAT
AQ
RH
CFD
CHANGOVR
DI0
AI0
MIXD1
MIXD2
CCV1
CCV2
HCV1
HCV2
HEATING
COOLING
48
min
^F
1.0 - 20.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
%RH
0.0 - 100.0
%RH
0.0 - 100.0
CFM
0.0 - 5000.0
CFM
5000 - 5000
0.0 - 5000.0
0.0 - 5000.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
NOTE: Alarm retry time (in the event an alarm is not acknowledged)
is fixed at 5 minutes.
STATUS / UNITS
xxxxxx
ASCII*
Norm/Alarm
xxx.x
xxx.x
xxx.x
xxx.x
xxx.x
Off/On
xxxxxx
ASCII†
Off/On
High/Low
xxx.x
xxx.x
xxxx.x
CFM
xxx.x
Clean/Dirty
xxxx.x
xxx.x
%RH
Norm/Alarm
Fire shutdown
Norm/Alarm
Heat/Cool
Off/On
xx.x
Volts
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
Off/On
RANGE
DEFAULT
0 - 1*
11010000
1-255†
255
5.0
45.0
150.0
40.0
120.0
30.0
70.0
0.0
800.0
0.0
800.0
40.0
140.0
OVERRIDE
LIMITS
°F
–40.0 - 245.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
°F
–40.0 - 245.0
0 - 1**
0 - 1**
0 - 1**
%
%
0.0 - 5000.0
%
0.0 - 100.0
0 - 1**
0.0 - 5000.0
0.0 - 100.0
0 - 1**
0 - 1**
0 - 1**
0.0 - 10.0
0 - 1**
0 - 1**
0 - 1**
0 - 1**
0 - 1**
0 - 1**
0 - 1**
0 - 1**