When you push the Hi POWER button during cooling,
heating or AUTO, the air conditioner will start the following
operation.
• Cooling operation
Performs the cooling operation at +1.8°F (1°C) lower than
the setting temperature.
Only when the fan speed before the Hi POWER operation
is not high, the fan speed will be increased.
• Heating operation
Performs the heating operation at +3.6°F (2°C) higher
than the setting temperature.
Only when the fan speed before the Hi POWER operation
is not high, the fan speed will be increased.
When you push the COMFORT SLEEP button during
cooling, heating or AUTO, the air conditioner will start the
following operation.
The fan speed display will indicate AUTO and low speed will
be used.
• Cooling operation
In the operation suppression zone, where capacity is kept
to the minimum, overcooling is prevented by raising the
temperature setting by +1.8°F (1°C) after 1 hour and by
+3.6°F (2°C) after
2 hours of operation.
The room temperature is thus regulated between the
operation suppression zone and the set temperature.
When the OFF timer is simultaneously set, 1, 3, 5 and 9
hours appear by turns every pushing COMFORT SLEEP
button and one of them can be selected for OFF timer.
• Heating operation
In the operation suppression zone, where capacity is kept
to the minimum, overheating is prevented by lowering the
temperature setting by +1.8°F (1°C) after 1 hour and by
+3.6°F (2°C) after
2 hours of operation.
The room temperature is thus regulated between the set
temperature and the operation suppression zone.
When the OFF timer is simultaneously set, 1, 3, 5 and 9
hours appear by turns every pushing COMFORT SLEEP
button and one of them can be selected for OFF timer.
Operation suppression zone
+3.6˚F
[2˚C]
+1.8˚F
[1˚C]
1 hour
2 hours
Set temperature
– 61 –
Remarks
• [Hi POWER] Display
• [
] display
Set temperature
+3.6˚F
+1.8˚F
[2˚C]
[1˚C]
1 hour
2 hours
Operation
suppression zone