Carrier RAV-SP180UT-UL Service Manual page 109

Split type
Hide thumbs Also See for Carrier RAV-SP180UT-UL:
Table of Contents

Advertisement

CODE No.(DN)
01
Filter sign lighting time
02
Filter pollution leve
03
Central control address
06
Heating suction temperature shift
0F
Cooling only
10
Type
11
Indoor unit capacity
12
System address
13
Indoor unit address
14
Group address
19
Louver type (wind direction adjustment)
Temperature range of cooling/heating
1E
automatic SW control point
28
AUTO restart
2A
Option/Abnormal input (CN70) SW
2b
Thermo output SW (T10
31
Ventilation fan (standalone)
32
Sensor SW (Selection of static pressure)
33
Temperature display SW
40
Humidifier control (+ drain pump control)
5d
High ceiling SW
60
Timer setting (wired remote controller)
Demand setting
C2
(outdoor unit current demand)
d0
Remote controller operation save function
d3
Rotation number of the self-clean operation
d1
Frost protection function
F0
Swing mode
F1
Louver fixing position (Flap No. 1)
F2
Louver fixing position (Flap No. 2)
F3
Louver fixing position (Flap No. 3)
F4
Louver fixing position (Flap No. 4)
Table 2. Type: CODE No. 10
SET DATA
0001
4-way Air Discharge Cassette Type
*1
0007
Under Ceiling Type
∗1 EEPROM initial value on the P .C. board for indoor unit servicing
Table 1. SET DATA (CODE No. table (example))
Item
ƒ
)
Type
Type name abb.
RAV-SP∗∗∗UT-UL
RAV-SP∗∗∗CT-UL
SET DATA
Depending on Type
0000: standard
0099: Not determined
0002: +2°C
(flooring installation type: 0)
0000: Heat pump
Depending on model type
Depending on capacity type
0099: Not determined
0099: Not determined
0099: Not determined
Depending on Type.
0003: 3 deg (Ts ± 1.5)
0001: Provided
0002: Humidifier
0000: Thermo ON
0000: Not available
0000: Body sensor
0001: °F
0003: Humidifier ON + Pump OFF
0000: Standard
0000: Available
0075: 75 %
0001: Enable
0001: 210ypm(at self-clean operation)
0000: None
0001: Standard
0000: Not fixed
0000: Not fixed
0000: Not fixed
0000: Not fixed
Indoor unit capacity: CODE No. 11
∗ EEPROM initial value on the P .C. board
for indoor unit servicing.
– 109 –
Factory-set value
Table 3.
SET DATA
Type
0000∗
Disable
0009
180
0012
240
0015
300
0017
360, 420

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Carrier rav-sp240ut-ulCarrier rav-sp180ct-ulCarrier rav-sp300ut-ulCarrier rav-sp240ct-ulCarrier rav-sp300ct-ulCarrier rav-sp360ct-ul ... Show all