CODE No.
Item
(DN)
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0C
Preparing indication selection
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
In automatic cooling/heating, temp.
1E
width of cool → heat, heat →
cool mode selection control point
28
Auto restart
Selection of option / error input
2A
(CN80)
Selection of thermostat output
2b
(T10
)
2E
Selection of HA (T10
31
Fan (Single operation)
32
Sensor selection
Timer setting
60
(Wired remote controller)
69
Louver setting for cooling
Correction of feeling
86
of strong heating
∗ The swing mode selection (CODE No. (DN) [F0]), louver fix (CODE No. (DN) [F1] to [F4]) and restriction ratio
setting for save operation (CODE No. (DN) [C2]) can be set/changed from the normal CODE No. (DN) setup
(Detail CODE No. (DN) setup).
Function selection CODE No. (DN) list
0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
0099: Undecided
0000: No shift
0002: 3.6°F [+2°C]
0000: Preparing indicated
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0001: 4-way air discharge cassette
0004: Concealed duct
0007: Under ceiling
0000: Undecided
0001: No.1 unit
0001: No.1 unit
0000: Individual
0002: Follower unit in group
0000: 0 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0000: Filter input
0002: External alarm input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
) terminal
0002: Fire alarm input
0000: Impossible
0000: Body TA sensor
0001: Remote controller sensor
0000: Operable
0000: Normal
0000: Not priovided
Contents
0001: 150H
0003: 5000H
0005: Clogging sensor used
to
0064: No.64 unit
0001: 1.8°F [+1°C]
to
0010: 18°F [+10°C]
(Up to +6 is recommended.)
0001: No indication
0008: High wall
0001 to 0034
to
0030: No.30 unit
to
0064: No.64 unit
0001: Master unit in group
to
0010: 10 deg
0001: Provided
0001: Alarm input
(Air cleaner, etc.)
0001: Card input
(Forgotten to be off)
0001: Possible
0001: Operation prohibited
0001: Down allowed
0001: Priovided
– 134 –
At shipment
from factory
0001: 150H
0000: Standard
0099: Undecided
0002: 3.6°F [+2°C]
0000: Preparing indicated
0000: Heat pump
0008: High wall
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
0003: 3 deg
(Ts±1.5)
0001: Provided
0002: External alarm input
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Body sensor
0000: Operable
0000: Normal
0000: Not priovided