CODE No. (DN)
01
Filter sign lighting time
02
Filter stain level
03
Central control address
06
Heating suction temp. shift
0F
Cooling-only
10
Type
11
Indoor unit capacity
12
Line address
13
Indoor unit address
14
Group address
Louver type
19
(Adjustment of air direction)
In automatic cooling/heating, temp.
1E
width of cool → heat, heat → cool
mode selection control point
28
Auto restart
Selection of option / error input
2A
(CN70)
Selection of thermostat output
2b
ƒ
(T10
)
2E
Selection of HA (T10) terminal
31
Fan (Single operation)
32
Sensor selection
33
Temperature display SW
High ceiling selection
5d
(Air volume selection)
Timer setting
60
(Wired remote controller)
Function selection CODE No. (DN) list
Item
0000: None
0002: 2500H
0004: 10000H
0000: Standard
0001: Heavy stain (Half of standard time)
0001: No.1 unit
0099: Undecided
0000: No shift
0002: 3.6°F [+2°C]
0000: Heat pump
0001: Cooling only (No display for [AUTO] [HEAT] )
0001: (4-way air discharge cassette)
0007: (Under ceiling)
0000: Undecided
0001: No.1 unit
0001: No.1 unit
0000: Individual
0002: Follower unit in group
0000: No louver model
(0002:1-way)
0004: 4-way
0000: 0 deg
(Cool/heat are reversed with ± (Data value) /
2 against the set temperature)
0000: None
0000: Filter input
0002: Humidifier input
0000: Indoor thermostat ON
0001: ON receiving output of outdoor compressor
0000: Normal (JEMA)
0002: Fire alarm input
0000: Impossible
0000: Body TA sensor
0001: Remote controller sensor
0000: °C
0000: Standard filter
0001: Super long life
0003: High performance (65%), High performance (90%),
(0006:Deodorant, Ammonia deodorization)
0000: Operable
Contents
0001: 150H
0003: 5000H
0005: Clogging sensor used
to
0064: No.64 unit
0001: 1.8°F [+1°C]
to
0010: 18°F [+10°C]
(Up to +6 is recommended.)
0001 to 0034
to
0030: No.30 unit
to
0064: No.64 unit
0001: Header unit in group
0001: Swing only
(0003:
to
0010: 10 deg
0001: Provided
0001: Alarm input
(Air cleaner, etc.)
0001: Card input
(Forgotten to be off)
0001: Possible
0001: °F
0001: Operation prohibited
– 121 –
At shipment from factory
According to type
0000: Standard
0099: Undecided
0002: 3.6°F [+2°C]
0000: Heat pump
According to model type
According to capacity type
0099: Undecided
0099: Undecided
0099: Undecided
2-way)
According to model type
0003: 3 deg
(Ts±1.5)
0001: Provided
0002: Humidifier
0000: Thermostat ON
0000: Normal
(HA terminal)
0000: Impossible
0000: Body sensor
0001: °F
0000: Standard
0000: Operable