No.
Item
6
Fan speed control
(Continued)
3) In heating operation, the mode changes to [UL] if thermostat is turned off.
4) If Ta ≥ 77°F (25°C) when heating operation has started and when defrost opera-
tion has been cleared, the air conditioner operates with (H) mode or higher mode
for 1 minute after Tc entered in E zone of cool air discharge preventive control (No. 7).
5) In automatic cooling/heating operation, the revolution frequency of (HH) is set
larger than that in the standard cooling/heating operation.
6) Self-clean operation (4-Way Discharge Cassette Type only)
When performing self-clean operation after stopping the cooling operation, the
mode becomes 210 rpm.
Outline of specifications
Standard
CODE No.
[5d]
0
SW501 (1)/(2)
OFF/OFF
Tap
HEAT COOL HEAT COOL HEAT COOL HEAT COOL
F1
F2
F3
F4
F5
HH
F6
HH
F7
H+
H+
F8
H
F9
H
FA
L+
FB
L+
L
FC
L
FD
UL
<4-Way Air Discharge Cassette Type>
SP180
Tap
F1
610
F2
560
F3
510
F4
460
F5
410
F6
400
F7
380
F8
360
F9
350
FA
340
FB
330
FC
320
FD
250
<Under Ceiling Type>
SP180
Tap
F1
1120
F2
1100
F3
1020
F4
990
F5
950
F6
930
F7
880
F8
840
F9
820
FA
800
FB
780
FC
760
FD
550
F5 → F4
Ta
˚F [˚C]
116.6 [47]
107.6 [42]
F5
Type 1
Type 3
1
3
ON/OFF
OFF/ON
HH
HH
HH
HH
H+, H H+, H H+, H H+, H
H+
H+
H
H
L+
L+
L
L
L+
L+
L
L
UL
UL
SP240
SP300
Revolution speed (rpm)
630
700
600
680
540
670
470
650
460
630
450
620
420
560
390
500
380
490
360
460
330
400
320
400
250
300
SP240
SP300
Revolution speed (rpm)
1140
1240
1100
1200
1060
1140
1020
1080
970
1040
960
1000
920
960
900
930
880
900
850
870
810
830
790
800
560
590
However the revolution
frequency is restricted in
the automatic heating
operation as shown in
the following figure.
– 42 –
Remarks
Type 6
Selection of high
6
ceiling type
ON/ON
CODE No.:
HH
HH
[5d] or selection of
high ceiling on P .C.
L+, L
L+, L
board SW501
UL
SP360, 420
700
680
670
660
650
640
570
500
490
470
430
420
300
SP360, 420
1300
1240
1200
1160
1120
1080
1040
990
960
950
890
860
590
However only when
the high ceiling
selection is set to
[Standard]
[Self-clean
displayed.
] is