Carrier RAV-SP180UT-UL Service Manual page 122

Split type
Hide thumbs Also See for Carrier RAV-SP180UT-UL:
Table of Contents

Advertisement

CODE No.
(DN)
Self-clean operation time
42
(4-Way Air Discharge Cassette Type only)
Selection of louver horizontal discharge
45
position
(4-Way Air Discharge Cassette Type only)
C2
Current demand X% to outdoor unit
Setting of self-clean operation forced
stop
CC
(4-Way Air Discharge Cassette Type only)
Clean operation stop function when
CD
[ON/OFF] operation is prohibited.
(4-Way Air Discharge Cassette Type only)
Existence of remote controller save
D0
function
Existence of 46°F (8°C) heating
D1
operation function
Revolution frequency of self clean
D3
operation
(4-Way Air Discharge Cassette Type only)
Display / No display of [Dry operation]
D4
during self clean operation
(4-Way Air Discharge Cassette Type only)
F0
Louver swing mode
F1
Louver No.1 fixed position
F2
Louver No.2 fixed position
F3
Louver No.3 fixed position
F4
Louver No.4 fixed position
∗ The swing mode selection (DN code No. [F0]), louver fix (DN code No. [F1] to [F4]) and restriction ratio setting for
save operation (DN code No. [C2]) can be set/changed from the normal DN setup (Detail DN setup).
Item
0000: None
Set when compressor-ON time is 10 to 60 minutes.
When ON-time is 60 minutes or more,
the double of this operation time setting is set.
0000: Smudging-less setting
0002: Cold draft preventive setting
0050: 50%
0000: No
• Clean operation is performed in case of stop by HA input.
• HA operation output OFF during clean operation in case
of stop by remote controller
0001: Yes
• Clean operation is not performed in case of stop by HA
input.
• HA operation output ON during clean operation in case of
stop by remote controller
The air conditioner stops (including fire alarm such as
remote monitor system) while setup of [ON/OFF] operation
prohibited (Central 1, 2) is performed from the central
controller side.
0000: Valid (Clean operation)
0001: Invalid (No clean operation)
0000: Invalid (Impossible)
0001: Valid (Possible)
0000: Invalid (Impossible)
0001: Valid (Possible)
0000: Invalid (Self clean operation is not carried out.)
0001: Valid (Self clean operation is practiced with 210 rpm.)
0000: Display
0000: No synchronization
0001: 4-way synchronization
0002: Dual
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
0000: Release (Free)
0001 to 0005: Horizontal discharge position to
Contents
0000: 0.5 h to 0.012: 0 h
to
0100: 100%
0001: No display
0003: Cycle
Downward discharge position
Downward discharge position
Downward discharge position
Downward discharge position
– 122 –
At shipment
from factory
0002: 1 hour
0000: Smudging-less
setting
0075: 75%
0000: None
0000: Valid
0001: Valid (Possible)
0001: Invalid (Impossible)
0001: Valid
(210 rpm / operation)
0000: Display
0001: 4-way
synchronization
0000: Release
0000: Release
0000: Release
0000: Release