6.5.5
Grid Support service menu
Grid support
Remote
Cosine Phi
Reactive
power
Cosine Phi(P)
Q(U)
Q(U) hysteresis Q(U) closed-loop control according to the curve saved in the
6.5.6
Power Reduction service menu
Power reduction
Maximum
power
This menu can only be changed for a period of 4 hours after initial con-
figuration.
36
In this setting, grid support is set by a remote device (e.g. PLATI-
NUM® WebMaster).
Enter cosine phi.
▪ Cosine Phi
▪ Type
▪ Phi
Enter the reactive power.
▪ % P_Nom
▪ Type
▪ Reactive power Associated reactive power
In this setting, cosine phi is configured according to the specifica-
tions defined in the PLATINUM® inverter.
Mains voltage-dependent reactive power regulation
▪ 102.0% is typical.
inverter. The curve can be parametrised via the PLATINUM® service
tool.
Enter the maximum power for this inverter according to the specifi-
cations of the network operator.
Installation and user guide PLATINUM® inverter 5500 R3-S2, 7000 R3-S2, 8000 R3-S2, 9000 R3-S2
0.707 ... 1
Capacitive (over-excited), inductive (under-
excited)
Associated angle
0 ... 50
Capacitive (over-excited), inductive (under-
excited)