Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove
to Combustibles
See figs. 2-3.
Rear:
2" (51 mm) - measured from Draft Hood
Ceiling:
32 1/4" (819 mm) - measured from stove top
Corner:
3" (76 mm) - measured from stove top
Sides:
3" (76 mm) - measured from stove top
Minimum Clearances from the Vent Pipe to
Combustibles
Horizontal Run:
Top:
Off the top of the pipe
Sides: Off the sides and bottom 2" (50 mm)
Vertical Run:
All sides: 1" (25 mm)
All vent components must be installed in accordance
with the manufacturer's instructions and within the
terms of their listing. Refer to the manufacturer's instruc-
tions for approved clearances from the vent pipe to
combustible materials.
Minimum Alcove Dimensions
Maintain clearances to combustibles as noted above.
Width:
36" (914 mm)
Depth:
24" (610 mm)
Height:
61" (1550 mm)
Mantel Clearances -
56 3/4
53 3/4
50 3/4
1441 mm
1365 mm
1289 mm
55 1/4
27 3/4
52 1/4
1403 mm
1327 mm
705 mm
Figure 4. Mantel and Trim specifications -
Stove installed flush with fireplace face.
2" (50 mm)
Stove shown with standard legs. With Short Legs, subtract 2 1/4" (51 mm)
from the clearances indicated below.
Max. Mantel Depth
11.5
9.5
7.5
5.5
3.5
Min. Mantel Depth
Max. Top Trim
Depth = 1
1
11
(266 mm)
3"
(76 mm)
Figure 2. Parallel Installation Clearances.
3
(76 mm)
Figure 3. Vent adaptor centerline at minimum clearance
to corner walls.
705 mm
Figure 4a. Mantel specifications -
Stove recessed into fireplace no more than 6 1/2".
2"
(51 mm)
To Rear Wall
3"
(76 mm)
11 3/4
(298 mm)
34
11 3/4
(864 mm)
(298 mm)
3
(76 mm)
Mantel Depths
Mantel Sheild:
as in Fig.4.
Min. 24 ga. steel
26 wide on 1
spacers
No Top Trim
27 3/4
7