Rack Installation - Liebert ITA UPS 16kVA User Manual

Ita ups 16kva/20kva
Table of Contents

Advertisement

2.4.2 Rack Installation

Installation procedures for battery modules excluded
1. Take out eight M4*10 screws, and fix two brackets (accessories) respectively on both sides of the UPS front panel,
as shown in Figure 2-3.
Moving the UPS through brackets is prohibited.
2. Place the UPS onto the guide rails in the rack, and push it completely into the rack. Take out four M6*16 screws to
fix the UPS on the rack through brackets, as shown in Figure 2-4.
Installation procedures for battery modules included
The installation method of the battery module is the same as that of the UPS. Repeat the above procedures to install
and fix the four battery modules and UPS on the rack one by one. As the battery module is heavy, you should pay
attention to the following items in installation:
z Two persons or more are required for the installation
z First install the battery module, then start the installation from the bottom, and place the UPS onto the top, as
shown in Figure 2-5
z Moving the UPS and battery modules through brackets is prohibited
UPS
Bracket (2 pcs)
Figure 2-3 Installing brackets
Rack
UPS
Bracket
Screw (4 pcs)
Figure 2-4 Installing the UPS
Liebert ITA 16kVA/20kVA User Manual
Screw (8 pcs)
Note
Guide rail
Chapter 2 Installation
9

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ita ups 20kvaUha3r-0160lUha3r-0200l