Liebert ITA UPS 16kVA User Manual page 36

Ita ups 16kva/20kva
Table of Contents

Advertisement

28
Chapter 3 Operation And Display Panel
Menu
Function settings
Test command (start, stop
battery, system test or
frocing boost charge)
System version
Keypad window
The function of menu buttons (F1 ~ F4 and HELP) is shown in icon mode for the current display screen.
Item
LCD contrast
Adjust the LCD contrast
YYYY MM DD, DD MM YYYY and MM DD YYYY formats can be
Date format
selected.
Date & time
Set the date and time
Comm1 baud rate
Set the communication baud rate of the USB port
Comm2 baud rate
For internal communication only, can not be set
Comm3 baud rate
Set the communication baud rate of the SNMP card port
UPS address
This setting is suitable for RS485 communication
Communication mode
Set the communication mode
If the communication mode of the SNMP card port is Modem, you can
Callback times
set alarm callback times here
If the communication mode of the SNMP card port is Modem, you can
Phone No.1
set phone No.1 here
If the communication mode of the SNMP card port is Modem, you can
Phone No.2
set phone No.2 here
If the communication mode of the SNMP card port is Modem, you can
Phone No.3
set phone No.3 here
Command password
You can change the command password. Default: "123456"
Battery capacity test
Battery capacity
Set the battery cell. The setting options include: 30-cell, 32-cell,
Battery cell
34-cell, 36-cell, 38-cell, 40-cell
Battery boost charge
Enabled or disenabled
Temperature
Enabled or disabled
compensation
Temperature sensor
Set the position of the temperature sensor. "Remote" only
Battery group sharing
Set each single in parallel system to share the battery group or not
Single/parallel
Set the single/parallel
Parallel number
Set the parallel number
Redundant number
Set the redudant number
ECO mode
ECO function enabled
Output frequency
Set the output frequency
Output voltage system
Set the output voltage system
LBS
LBS function enabled
Set the output system: 3-in 3-out/3-in 3-out
This setting can only be carried out after the EPO operation. After the
3-in 3-out/3-in 3-out
setting, you must power off the system, and confirm that the system
actual connection mode complies with the setting. Power on again,
and the setting can come into force
The battery maintenance test will lead to the battery being partly
Battery maintenance
discharged, for rough assessment of the battery capacity. The load
test
must range from 20% ~ 100%
The battery capacity test will lead to the battery being completely
Battery capacity test
discharged, for accurate assessment of the battery capacity. The load
must range from 20% ~ 100%
For UPS self-test. The user actives this function, 5 seconds later, a
System test
pop window will appear to show the result of this test
Manually stop the test, including maintenance test, capacity test and
Stop testing
system test
Forcing charge
Manually conduct the forcing boost charge for battery
Stop forcing charge
Manually stop the forcing boost charge for battery
Monitor Version
Provide the monitor software version
Rectifier Version
Provide the rectifier software version
Inverter Version
Provide the inverter software version
Liebert ITA 16kVA/20kVA User Manual