Thermocouple And Power Unit Tests - L.B. White Pilot Light Ignition Installation And Service Manual

Pilot light ignition agricultural animal confinement building heaters
Hide thumbs Also See for Pilot Light Ignition:
Table of Contents

Advertisement

Component
Testing

Thermocouple and Power Unit Tests

Equipment R R equired:
Volt / Ohm Meter with DC Scale
Thermocouple Test Kit, Part Number 500-08506
The thermocouple is used in conjunction with the pilot safety
control valve in supplying pilot gas to the pilot orifice.
Here i i s H H ow i i t W W orks:
A thermocouple converts heat energy into electrical energy.
When the tip of the thermocouple is properly positioned in
the pilot flame, the temperature difference between the hot
and cold junction generates a small amount of electrical
energy in the form of direct current (DC) which is fed into the
spring-loaded power unit within the control valve.
current holds the power unit open to allow gas to be fed to
the pilot orifice.
C C O O L L D D
J J U U N N C C T T I I O O N N
H H O O T T J J U U N N C C T T I I O O N N
T T H H E E R R M M O O C C O O U U P P L L E E
C C O O N N N N E E C C T T O O R R N N U U T T
P P O O W W E E R R U U N N I I T T
C C O O N N N N E E C C T T O O R R
C C O O N N T T A A C C T T
As long as the pilot gas stays lit and the pilot flame is
directed to the thermocouple, the thermocouple will
continue to create the small amount of electrical energy
necessary to keep the power unit open.
illustration shows the electrical circuit of the thermocouple
with its relationship to the pilot safety control valve.
6.3-1 1
The
M M O O U U N N T T I I N N G G
C C L L I I P P
O O P P T T I I O O N N A A L L
A A T T T T A A C C H H M M E E N N T T
N N U U T T
C C U U R R R R E E N N T T C C O O N N D D U U C C T T O O R R S S
I I N N S S U U L L A A T T E E D D W W I I R R E E
C C O O P P P P E E R R T T U U B B I I N N G G
The following
PILOT
BURNER
THERMOCOUPLE
LEAD
SAFETY V V ALVE
PLUNGER
If the pilot flame is extinguished, or is too small to reliably
heat the thermocouple, the DC output being generated
drops below the minimum level required to hold the power
unit open. The spring within the power unit pushes down the
safety valve plunger, thereby discontinuing the flow of gas to
the pilot and main burner.
If pilot outage problems are occurring, there are several
steps that you must complete before assuming the
thermocouple, or the pilot safety control valve are defective.
These are as follows:
Check inlet pressures to the control valve to make sure
the pressure is within parameters specified on the
heater's dataplate.
Clean the pilot assembly components, or if necessary,
replace the pilot orifice if it is plugged.
Insure that dirt is not located between the
thermocouple's power unit contact and power unit
within the safety control valve.
Insure that the thermocouple is properly positioned
within the pilot burner bracket, that the pilot flame
envelopes
the
thermocouple's
thermocouple's contact is snugged at the gas control
valve. (Tighten finger tight plus 1/4 turn.)
The pilot shield must be tight against the burner
casting.
The pilot gasket (if applicable) is properly installed
between pilot shield and casting.
If these items are satisfactory, then proceed to check
both the DC output strength of the thermocouple and
drop-out strength of the electromagnet within the
power unit of the pilot safety control valve.
THERMOCOUPLE
P P O O W W E E R R
U U N N I I T T
C C O O I I L L
tip
and
August 1999