Forced air heater, lp vapor withdrawal or natural gas (120 pages)
Summary of Contents for L.B. White FUEL HD120
Page 1
Owner's Manual and Instructions ™ GreenGro Plus Greenhouse Heaters MODELS OUTPUT (Btuh) FUEL Available in either HD120 120,000 L.P. Gas Vapor Withdrawal or Natural Gas Configurations. Congratulations! You have purchased the finest direct fired greenhouse heater available. Your new L.B. White heater incorporates the benefits from the most experienced manufacturer of heating products using state-of-the-art technology.
Page 3
Failure to comply with the precautions and instructions provided with this heater, can result in: — Death — Serious bodily injury or burns — Property damage or loss from fire or explosion — Asphyxiation due to lack of adequate air supply or carbon monoxide poisoning —...
SPECIFICATIONS Maximum Input (BTUH) Minimum Input (BTUH) EXHAUST FAN Indoor Mounting Air Exchange Requirements SHUTTERED AIR INLET Outdoor Mounting Air SHUTTERED Exchange Requirements EXHAUST OUTLET Inlet Gas Supply MAX. Pressure Acceptable at the Inlet of the Heater for Purpose of Input MIN.
Safety Precautions Do not use this heater for heating human living quarters. Do not use in areas without proper air exchange. See air exchange requirements on page 4 or on heater’s dataplate. Exhaust fans, supply air inlets, or exhaust fan outlets must not be obstructed.
Page 7
1. Do not attempt to install, repair, or service this heater or the gas supply line unless you have continuing expert training and knowledge of gas heaters. Qualifications for service and installation of this equipment are as follows: a. To be a qualified gas heater service person, you must have sufficient training and experience to handle all aspects of gas-fired heater installation, service and repair.
Refer to instructions provided in the optional L.B. White outdoor mounting and ducting kit, part number 23578. 4. The heater must have the proper gas regulator installed for the application.
-- With the main burner in operation, check all connections, hose connections, fittings and joints as well as the gas control valve inlet and outlet connections with approved gas leak detectors. -- If a leak is detected, check the components involved for cleanliness in the thread areas and proper application of pipe compound before further tightening.
INDOOR INSTALLATION INSTRUCTIONS This heater may be mounted within the greenhouse for indoor heating applications. The heater may be installed on an optional indoor mounting bracket kit, part number 23651, which is installed on freestanding supports or mounted directly to the structure’s wall. Separate installation instructions accompany the kit.
NIPPLE HOSE ADAPTER TO GAS CONTROL NIPPLE THERMOSTAT YELLOW BLACK BLUE WHITE GREEN...
Page 12
B. Single S S tage T T hermostat 1. Operate on first stage heat only. -- Remove jumper at terminals 8 and 9. -- Connect thermostat to terminals 8 and 9. THERMOSTAT WHITE WHITE BLACK 2. Operate on second stage heat only. -- Remove jumper at terminals 8 and 9.
VENT MODE -- Remove black lead at terminal 4 to selector switch. -- Add contacts at terminals 1 and 4. VENT MODE CONTACTS BLACK BLACK BLACK WHITE SELECTOR SWITCH GREEN POWER CORD TERMINAL STRIP 1. Always use approved pipe thread compound suitable for use with L.P.
Start-Up Instructions For initial start-up after heater installation, follow steps 1-6. For normal start-up, simply set the thermostat above room temperature. Connect electrical cord to an approved electrical outlet. 2. Set thermostat to desired room temperature. 3. This heater has a manually operated toggle style selector switch located on the top of the control box.
This heater contains electrical and mechanical components in the gas management, and safety systems. Such components may become inoperative or fail due to dust, dirt, wear and aging. Periodic cleaning and inspection as well as proper maintenance are essential to avoid serious injury or property damage.
Service Instructions GENERAL WARNING B B u u r r n n H H a a z z a a r r d d Heater surfaces are hot for a period of time after the heater has been shut down. Allow the heater to cool before performing service, maintenance, or cleaning.
1. Ensure there is not any dust, dirt, etc. that may cause binding on the pivot points of the flapper. If debris is found, use a soft brush, or compressed air, to clean the area as necessary. 2. The arm of the flapper should engage the arm of the airflow switch when the trailing edge of the flapper body is lifted and is at the proper clearance distance off the blower housing bottom.
TESTING THE MANUAL RESET HIGH LIMIT SWITCH WARNING Fire H H azard Do not operate the heater with the high limit switch bypassed. Operating the heater with a bypassed high limit switch may lead to overheating, possibly resulting in a fire, with subsequent damage to the heater, building damage, or loss of plants.
ATTENTION The following explains a typical procedure to be followed in checking gas pressures. Consult the dataplate on the heater or page 4 in this manual for specific pressures to be used in conjunction with this procedure. The gas pressures will vary depending upon fuel type.
Troubleshooting Instructions READ THIS ENTIRE SECTION BEFORE BEGINNING TO TROUBLESHOOT PROBLEMS. WARNING This heater can start at any time. Troubleshooting this system may require operating the unit with line voltage present and gas on. Use extreme caution when working on the heater. Failure to follow this warning may result in personal injury or death.
Electrical Connection and Ladder Diagram CAUTION-REFER TO THE HEATER’S ELECTRICAL CONNECTION DIAGRAM WHEN SERVICING TO AVOID WIRING ERRORS AND HEATER MALFUNCTION. CHECK FOR PROPER OPERATION AFTER SERVICING. BLACK WHITE GREEN POWER CORD GROUND TRANSFORMER BLACK WHITE IGNITER FLAME SENSOR BURNER HIGH VOLTAGE GROUND IGNITION LEAD...
Air Proving Switch Safety device used to insure that the proper air flow is being achieved before the gas valve is opened. Burner Cast iron component used to channel gas and provide an area at which the fuel may ignite. Burner Orifice Brass metering device used to feed gas to burner at a specific rate.
Item Description Regulator, LP Gas, 2nd Stage, Vent Over Outlet Regulator, LP Gas, 2nd Stage, Vent Over Side Regulator, Natural Gas (5 PSIG Inlet, 13.5 Outlet) Nipple, 3 1/2 in. Valve, Manual Shut Off Hose, 1/2 in. ID x 10 ft. with Adapter Adapter, Hose, 1/2 NPT x 1/2 NPS Kit, Sediment Trap Base...
Warranty Policy HEATER L.B. White Co., Inc. warrants that the component parts of its heater are free from defects in material and workmanship, when properly installed, operated, and maintained in accordance with the Installation and Maintenance Instructions, safety guides and labels contained with each unit.