ATTENTION
The following is supplied for informational purposes
only.
All electrical wiring shall be accomplished by a
qualified electrician.
Local and state codes must be observed at all times.
In absence of local or state codes, follow
ANSI/NFPA70 National Electrical Code.
August 1999
Strict attention must be given to the following areas before
connecting the heater to its electrical supply.
A properly installed three-wire electrical supply
consisting of separate hot, neutral, and ground leads
shall be connected to each electrical outlet that
supplies each heater.
Proper voltage must be supplied to each heater.
-- Proper voltage is 115 V.A.C.
+10% (127 volts maximum)
- 15% (98 volts minimum)
-- Under voltage may cause:
*
Low motor speed
*
High limit switch tripping
*
Burner flame cycling on/off
*
Control valve solenoid hums
or does not open.
-- Over voltage may cause:
*
Motor thermal overload tripping
A three-wire cord set (consisting of hot, neutral and
ground leads) of proper wire gauge and desired
length, must be obtained through local sources when
connecting a remote mount thermostat to the heater.
Installation
Instructions
Electrical Requirements
2.8-1 1