Aswh / Asdh - Asdh / Asdc Wall - Duct Temperature/Humidity Sensors - Carel UE001 Installation Operation User Manual

Humisteam electrode steam humidifiers
Hide thumbs Also See for UE001:
Table of Contents

Advertisement

CAREL
ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
Model
Humidity (0-1 VDC or 4-20 mADC)
ASWH100000 Wall Humidity s ensor (replaces SHWOOP)
ASDH100000 Duct Humidity sensor (repl aces SSDOMH00/1)
Temperature & Humidity (NTC temp, 0- 1 VDC or 4-20 mADC humidity)
ASWC111000 Wall Temp/hum s ens or (replaces SWNTCTH0/1 & STHONTC0/1)
ASWC110000 Wall Temp/hum s ens or (replaces STHOAP)
Temperature & Humidity (0-1 VDC or 4-20 Mad c temp & humidity)
ASDC111000 Duct temp/hum s ens or (replac es SDNTCTH0/1)
ASDC110000 Duct temp/hum s ens or (replac es SSDOMHT0/1)
Description
20
humiSteam
Temperature: NTC thermistor, 10 Kohm at 25° C (77° F)
(ASWC/ASDC onl y)
Accurac y: +- 0.25° C from 0 to 50° C (32 to 122° F)
Humidity: Thi n film capacitor
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accurac y: +- 3%RH fr om 20 to 90%RH
calibrated at 55%RH and 25° C (77° F)
+- 5%RH above 90%RH and below 20%RH
Response tim e: 60 sec onds
Power: 12 to 24 Vac/dc or +12 to –12 Vdc
Housing: Wall: ABS with glassfiber fill
Certifications: Calibrated to NIST trac eable
humidity/temperature s tandar d, CE Approved