SD
14.1. ASWH / ASDH – ASDH / ASDC Wall – Duct Temperature/Humidity Sensors
Model
Humidity (0-1 VDC or 4-20 mADC)
ASWH100000
Wall Humidity sensor (replaces SHWOOP)
ASDH100000
Duct Humidity sensor (replaces SSDOMH00/1)
Temperature & Humidity (NTC temp, 0-1 VDC or 4-20 mADC humidity)
ASWC111000
Wall Temp/hum sensor (replaces SWNTCTH0/1 & STHONTC0/1)
ASWC110000
Wall Temp/hum sensor (replaces STHOAP)
Temperature & Humidity (0-1 VDC or 4-20 Madc temp & humidity)
ASDC111000
Duct temp/hum sensor (replaces SDNTCTH0/1)
ASDC110000
Duct temp/hum sensor (replaces SSDOMHT0/1)
Description
39
Temperature: NTC thermistor, 10 Kohm at 25°C (77°F)
(ASWC/ASDC only)
Accuracy: +- 0.25°C from 0 to 50°C (32 to 122°F)
Humidity: Thin film capacitor
Linear 0-1 Vdc or 4-20 mAdc from 10 to 90%RH
Accuracy: +- 3%RH from 20 to 90%RH
calibrated at 55%RH and 25°C (77°F)
+- 5%RH above 90%RH and below 20%RH
Response time: 60 seconds
Power: 12 to 24 Vac/dc or +12 to –12 Vdc
Housing: Wall: ABS with glassfiber fill
Certifications: Calibrated to NIST traceable
humidity/temperature standard, CE Approved