1.5 Power wiring

Single Phase Terminals
Three Phase Terminals
Check that the power supply voltage to be
connected matches the value indicated on the
rating plate inside the electrical panel. Insert the
power and ground connection cables into the
electrical panel compartment using the strain
reliefs supplied, and connect to the terminals.
An external fused disconnect must be installed.
All w iring must be in accordance with local,
state and national electric codes.
NOTE: to avoid unwanted interference, the
power cables should be kept separate from any
control wiring.
Per the table on the following page, make sure
that the unit has the proper number of turns
through the TAM (Torroid Amperage Monitor),
which is on the control board in models UE001
through UE015, and separate in models UE025
through UE065. Also make sure that the TA
Rate DIP switches on the control board are set
correctly per the table.
In models UE001 - UE015 make sure that the TAM on the
circuit board has the proper number of power wire turns
through it, and that the TA Rate DIP switches on the
control board are set per the table on the following page.
In models UE025 - UE065 the TAM is independent and the jumper must then be on the right terminals per the
table on the following page.
15