Connect Power Wiring - Carel SD Installation & Maintenance Manual

Electronic steam humidifiers
Hide thumbs Also See for SD:
Table of Contents

Advertisement

SD
Carel USA

4. Connect Power Wiring

Before connecting any power supply, check the data label inside the electrical compartment
door to make sure the unit configuration matches the power supply. If it does not match, do
NOT connect power – call your Carel representative.
Insert the high power wires through the strain reliefs provided on the BOTTOM of the
humidifier and wire directly to the field wiring terminals as shown below without loops. DO
NOT bring high power wires into the humidifier from any other point. High power wires near
the low voltage controls can damage them and VOID WARRANTY. An external, fused
disconnect should be provided by the installer.
Each SD humidifier is internally wired for the maximum amperage that it can see on any voltage. Electrical wiring
sizes must match all national and local electrical codes. Generally, the following maximum wire sizes can be
connected to SD humidifiers:
SD MODELS
101
102
103
106
303
305
308
313
323
333
342
360
384
3B3
14
14
12
10
14
12
10
8
4
6
2
1
1/0
4/0
Max. Wire Size – Ga.
9

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents