Safety Considerations; Rack Warnings And Cautions; Preparation Procedures; Powering Down The Mcs Unit - HP 403349-003 Maintenance And Service Manual

Modular cooling system
Table of Contents

Advertisement

5-mm Allen wrench
o
Water temperature sensor
T-25 Torx driver
o
Phillips screwdriver
o
(2) 18-mm wrench
o
Wire cutters
o

Safety considerations

Before performing service procedures, review the following safety information.

Rack warnings and cautions

Before installing a spare kit, be sure that you understand the following warnings and cautions.
WARNING:
preparation guide, the user guide, and the maintenance and service guide. Failure to follow
the instructions listed in these guides can void your warranty and service contract.
WARNING:
caution when removing and replacing components that involve water around the electrical
wires and unsecured power inlet box. There is great risk of electrical shock when water is used
near electricity.
IMPORTANT:
rack attached to the MCS unit while completing the following procedures in order to increase
air flow within the rack.
IMPORTANT:
document, consult the site preparation guide and the user guide provided with the original unit
for a complete list of cautions and warnings.

Preparation procedures

Before you perform certain service procedures, perform one or both of the following procedures.

Powering down the MCS unit

Open the front MCS door.
1.
Turn off the AC1 and AC2 breakers on the AC transfer switch.
2.
Open the rear MCS door.
3.
You must follow the removal and replacement instructions listed in the site
To reduce the risk of electric shock or damage to the equipment, use extreme
To reduce the risk of the servers overheating, open all of the rack doors of each
While the most important cautions and warnings have been included in this
Removal and replacement procedures 24