Appendix A.2. 2. How Server Expects Data; Appendix A.2.1. Data_Type Is Ana_Input Or Not Specified; Appendix A.2.2. Data_Type Is Digi_Input - FieldServer FS-8700-127 Hanning Driver Manual

Fs-8700-127 hanning; kahl hcs-r
Hide thumbs Also See for FS-8700-127 Hanning:
Table of Contents

Advertisement

FS-8700-127 Hanning & Kahl HCS-R Manual
The same data will be stored in a Loop based Data Array which will then have the last
known data for each loop
Data Array Offset
Current Data
0 - 18
19
20
nd
2
(Previous) Data
21 – 39
40
41
rd
3
(Prior to previous) Data
42 – 60
61
62

Appendix A.2. 2. How Server expects Data:

The Server expects data in the following format in order to constitute its response to HCS-R
Clients.
Appendix A.2.1.
Data Array Offset
0 - 18
19
20
21
Appendix A.2.2.
Data Array Offset (say 0)
0 - 18
19
20
21,22
.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.FieldServer.com
Tel: 408 262-2299 Fax: 408-262-2269 Toll_Free: 888-509-1970 email: support@FieldServer.com
Description
Data bits ( 0 – 1)
Receipt ok ( 0 ), Disturbance ( 1 )
From Loop ( 0 ), On Loop ( 1 )
Data bits ( 0 – 1)
Receipt ok ( 0 ), Disturbance ( 1 )
From Loop ( 0 ), On Loop ( 1 )
Data bits ( 0 – 1)
Receipt ok ( 0 ), Disturbance ( 1 )
From Loop ( 0 ), On Loop ( 1 )
Data_Type is Ana_Input or not specified
Description
Data bits ( 0 - 1 )
Receipt ok ( 0 ), Disturbance ( 1 )
From Loop ( 0 ), On Loop ( 1 )
Loop Number (0,1,2,3)
Data_Type is Digi_Input
Description
Data bits ( 0 - 1 )
Receipt ok ( 0 ), Disturbance ( 1 )
From Loop ( 0 ), On Loop ( 1 )
2 bits for Loop Number
Offsets
21 22
0
0
–Loop 1
1
0
–Loop 2
0
1
–Loop 3
1
1
–Loop 4
Page 16 of 17