FS-8700-112 FCI 7100 Series Driver Manual
4.3.

Client Side Node Descriptors

Section Title
Nodes
Column Title
Node_Name
Node_ID
Protocol
FCI_Reset_Acti
on_Option*
Connection
Example
//
Client Side Nodes
Nodes
Node_Name,
Panel-01,
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Function
Provide name for node
This parameter only has meaning
for
this
driver
when
panels are networked in an FCI
network.
In
this
NODE_ID is the panel number.
Set the Node_ID of the local panel
to zero, and create one node
descriptor for each panel setting
the Node_ID to the panel number.
Specify protocol used
Only
required
for
configurations.
This parameter tells the driver
what to do with 'Reset' messages.
When not specified or set to
'Reset_by_any_Node ' then the
driver will reset the data array
points associated with the given
node irrespective of the reset
message's origin.
When
set
'Reset_by_this_Node_Only' then
the driver only resets the data
associated with the given node if
the reset originated from the same
node.
Specify which port the device is
connected to the FieldServer
Protocol,
FCI_7100,
Up to 32 alphanumeric characters
The protocol is node-less - the
multiple
messages
information identifying a unique
case
the
source and/or destination node
address. Thus this parameter need
not be specified if only one 7100 is
connected per FieldServer serial
port. In networked configurations,
specify whole numbers 0,1,2,3 ...
FCI_7100,
FCI7100
networked
Reset_by_any_Node,
Reset_by_this_Node_Only
to
P1-P8, R1-R2
Connection
P8
Page 9 of 24
Legal Values
do
not
contain
FCI_7100_series,
1