A Sierra Monitor Company Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-73 BACnet MSTP - Serial APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after August 2008 Driver Version: 1.00 Document Revision:...
Appendix C.3. Known problems with third party devices - Automated Logic Corporation..21 APPENDIX D. UNITS ......................22 FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
BACnet MSTP Description The BACnet Master-Slave/Token-Passing (MSTP) driver implements a data link protocol that uses the services of the RS-485 physical layer. See the FieldServer BACnet PIC statement for the level of conformance that this driver implements. Max Nodes Supported...
FieldServer RS-232 to RS-485 converter If FieldServer used as BACnet Client. If FieldServer used as BACnet Server FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
FS-8700-73 BACnet MSTP Driver Manual Page 5 of 24 Hardware Connections The FieldServer is connected to the BACnet MSTP as shown in connection drawing. Configure the BACnet MSTP according to manufacturer’s instructions FieldServer as a BACnet MSTP Client FieldServer Server n...
4.1. Data Arrays/Descriptors The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet MSTP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes”...
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
Legal Values Scan_Interval* Rate at which data is polled 0-32000, 2s Refer to Appendix A.1 for further information. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet MSTP Client. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet MSTP communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
For server configurations the Max_Master and Max_Info_Frames parameters (or properties) can be overridden from a BACnet Client by using the “Write Property” command. Note that when the FieldServer is restarted, the default values as specified in the configuration file will be applied Only one Server Nodes may be defined for each connection.
Page 14
Nodes Node_Name, Node_ID, Protocol Virtual_BCU_11, BACnet_MSTP Note that adapter is not declared in the Server Side Nodes FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
Refer to Appendix A.1 for further information. See the BACnet DFS to determine if a particular object supports this property FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: (888) 509-1970 email: support@fieldserver.com...
When BACnet Output objects are written to the Server side of the FieldServer, an associated write priority is given to each write value. When the FieldServer receives the write value, it stores it to the Map Descriptor Priority Array Table at the specified priority. The Priority Array Table is then scanned and the value with the highest priority is stored to the Data Array location specified by the Map Descriptor.
Client side of the FieldServer is not communicating. When new points are added to the FieldServer it is important to restart the Summit Workstation or •...
When connecting the FieldServer to an ALC BACnet/MSTP module, always start the FieldServer first. Wait until the RUN Led is flashing on the FieldServer before powering up the MSTP module. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com...