Driver Manual (Supplement to the FieldServer Instruction Manual) FS-8700-16 Bacnet PTP - Serial APPLICABILITY & EFFECTIVITY Effective for all systems manufactured after September 2008 Driver Version: 1.15 Document Revision:...
Page 3 of 20 BACnet Description The BACnet PTP driver allows the FieldServer to transfer data to and from devices using the BACnet protocol over a serial RS-232 physical layer. The FieldServer can emulate either a Server or Client. The information that follows describes how to expand upon the factory defaults provided in the configuration files included with the FieldServer.
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com...
4.1. Data Arrays/ Descriptors The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays” section, the destination device addresses need to be declared in the “Client Side Nodes”...
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction manual for details of the ports available on specific hardware. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com...
Column Title Function Legal Values Scan_Interval* Seconds per scan 0-32000, 2 Refer to Appendix A.1 for further information. FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com...
This section documents and describes the parameters necessary for configuring the FieldServer to communicate with a BACnet Client. The configuration file tells the FieldServer about its interfaces, and the routing of data required. In order to enable the FieldServer for BACnet communications, the driver independent FieldServer buffers need to be declared in the “Data Arrays”...
When using the Trane Tracer Summit Workstation System, this name will appear as the object name FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com Tel: (408) 262-2299 Fax: (408) 262-9042 Toll Free: 888-509-1970 email: support@fieldserver.com...
When BACnet Output objects are written to the Server side of the FieldServer, an associated write priority is given to each write value. When the FieldServer receives the write value, it will be stored to the Map Descriptor Priority Array Table at the specified priority. The Priority Array Table is then scanned and the value with the highest priority is stored to the Data Array location specified by the Map Descriptor.
Appendix B.4. Network number The default Network number of a FieldServer is 5. In order to ensure communication between the BACnet Client and all Servers on a BACnet network, however, it may be necessary to assign a unique network number to each FieldServer.
• the instance will overwrite the first one. This may cause a BACnet Object to be “lost.” If “Virtual_BCU_…” is not being indicated as the device description for the FieldServer on the • BACnet SCADA system, then the FieldServer is not communicating with the SCADA system.