FS-8700-112 FCI 7100 Series Driver Manual
Message
FCI7100:#28
Err.
Expected 1..99
FCI7100:#29 Err. Invalid Zone number. Expected
1..255
FCI7100:#30 Err. Invalid Relay number. Expected
1..255
FCI7100:#31 Err. Point Type Invalid.
FCI7100:#32 Err. No MD Length. Default to 1
FCI7100:#33 Err. Driver cant poll or write.
FCI7100:#36 Err. Too Short. Bytes=%d , conn-
>ux_iptr"
4
Correct the configuration file, download to the FieldServer and restart the FieldServer for the
changes to take effect.
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web:www.fieldserver.com
Tel: (408) 262-2299 Fax: (408) 262-9042 Toll_Free: 888-509-1970 email: support@fieldserver.com
Invalid
Sensor
number.
Description
Correct the configuration file.
Valid Point Types are listed in Section
4
4.4.2
You must specify the 'length' of each Map
Descriptor. Refer to Section 4.4.2
The driver can only listen passively for
message from the panel. Remove any
active
Map
Descriptors
configuration file.
An event message is less than 80 bytes
long. If this error is repeated often it is
possible that a FCI firmware update as
made the driver unusable. Take a log and
contact tech support.