Client Side Connection Descriptors; Client Side Node Descriptors - FieldServer FS-8700-39 EST3 ECP Instruction Manual

Est3 external communications protocol (ecp) driver
Table of Contents

Advertisement

FS-8700-39 EST3 Driver Manual
4.2.

Client Side Connection Descriptors

Section Title
Connections
Column Title
Port
Baud
Parity*
Data_Bits*
Protocol
Example
//
Client Side Connections
Connections
Port
P8
4.3.

Client Side Node Descriptors

Section Title
Nodes
Column Title
Node_Name
Provide name for Node
Node_ID
MAC ID of FieldServer
Protocol
Specify protocol used
Specify which port the device is connected to
Port
the FieldServer
Specify time allowed between poll and
Timeout
response
Example
//
Client Side Nodes
Nodes
Node_Name
EST_1
1
Not all ports shown are necessarily supported by the hardware. Consult the appropriate Instruction
manual for details of the ports available on specific hardware.
2
Edwards Recommends 19200-baud minimum in order to prevent buffer overruns in the EST3 panel
FieldServer Technologies 1991 Tarob Court Milpitas, California 95035 USA Web: www.fieldserver.com
Tel: (408) 262 2299 Fax: (408) 262 2269 Toll Free: (888) 509 1970 email: support@fieldserver.com
Specify which port the device is connected to the
FieldServer
Specify baud rate
Specify parity
Specify data bits
Specify protocol to be used by this port
,Baud
,Parity
,19200
,None
Function
,Node_ID
,Protocol
,1
,EST3
Function
,Data_Bits
,8
Up to 32 alphanumeric
characters
1 – 24 (normally 1)
EST3
P1-P8, R1-R2
≥10 seconds
,Port
,P8
Page 6 of 21
Legal Values
1
P1-P8, R1-R2
2
9600, 19200
None
8
EST3
,Protocol
,EST3
Legal Values
1
,Timeout
,10s

Advertisement

Table of Contents
loading

Table of Contents