List of Electrical and Functional Parts

1. List of Electrical and Functional Parts
1.1

Outdoor Units

Item
Compressor
Inverter
Motor
Fan motor
Overcurrent relay
Electronic expansion
valve
Functional
Four-way valve
parts
Solenoid valve (Hot gas)
Solenoid valve (Injection)
Pressure switch (INV.)
Pressure-
Fusible plug
related parts
Pressure sensor (HP)
Pressure sensor (LP)
For outdoor air
For discharge
Main
Thermistor
For suction 1
P.C.B.
For heat exchanger
For suction 2
9
Name
Symbol
Type
M1C
Output
M1F
Cooling
Y1E
Heating
Y1S
Y2S
Y3S
S1PH
S1NPH
S1NPL
R1T
R2T
R3T
R4T
R5T
Model
RZQ18
RZQ24
PVJU
PVJU
2YC63HXD#ED
1.7kW
0.07kW
3.2A
1400pls
PI control
STF-01AQ555A1
TEV-MOAQ1684Y1
TEV-MOAQ1685Y1
ACB-4UB10
ON: 580+0/-22 psi OFF: 435±22 psi
DFP-3L 158~167°F
NSK-BD042D~212 0~602 psi
NSK-BD017D-211 -7~247 psi
ST9303-4
ST9701-4
ST8602A-5
ST8604A-7
ST8604A-7
List of Electrical and Functional Parts
SiUS28-902_a
Remark
RZQ30
(P.C.B. terminal)
PVJU
A1P X21A
A1P X25A
A1P X26A
A1P X27A
A1P X32A
A1P X504A
A1P X503A
A1P X11A
A1P X12A 1-2Pin
A1P X12A 3-4Pin
A1P X12A 5-6Pin
A1P X12A 7-8Pin