SiUS28-902_a
E5
3.17 "
" Inverter Compressor Motor Lock
E5
Remote
Controller
Display
Applicable
RZQ18~30PVJU
Models
Method of
Inverter P.C.B. takes the position signal from UVW line connected between the inverter and
Malfunction
compressor, and the malfunction is detected when any abnormality is observed in the phase-
current waveform.
Detection
Malfunction
This malfunction will be output when the inverter compressor motor does not start up even in
Decision
forced startup mode.
Conditions
Compressor lock
Supposed
High differential pressure (72psi or more)
Causes
Incorrect UVW wiring
Faulty inverter P.C.B.
Stop valve is left in closed position.
Troubleshooting
Troubleshooting by Indication on the Remote Controller
106