Ja" Outdoor Unit: Malfunction Of High Pressure Sensor - Daikin FCQ18PVJU Service Manual

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

Troubleshooting by Indication on the Remote Controller
JA
3.26 "
" Outdoor Unit: Malfunction of High Pressure Sensor
JA
Remote
Controller
Display
Applicable
RZQ18~30PVJU
Models
Method of
Malfunction is detected from the pressure detected by the high pressure sensor.
Malfunction
Detection
Malfunction
When the high pressure sensor is short circuit or open circuit.
Decision
Conditions
 Defect of high pressure sensor
Supposed
 Connection of low pressure sensor with wrong connection.
Causes
 Defect of outdoor unit P.C.B.