Troubleshooting By Indication On; The Centralized Remote Controller; Ue" Malfunction Of Transmission Between Centralized Remote Controller And Indoor Unit - Daikin FCQ18PVJU Service Manual

Split system air conditioners skyair inverter r-410a heat pump 60hz p series
Hide thumbs Also See for FCQ18PVJU:
Table of Contents

Advertisement

Troubleshooting by Indication on the Centralized Remote Controller
4. Troubleshooting by Indication on the Centralized
Remote Controller
UE
4.1
"
" Malfunction of Transmission between Centralized
Remote Controller and Indoor Unit
UE
Remote Controller
Display
Applicable
AII indoor unit models
Models
Centralized Remote Controller
Method of
Microcomputer checks if transmission between indoor unit and centralized remote controller is
normal.
Malfunction
Detection
Malfunction
When transmission is not carried out normally for a certain amount of time
Decision
Conditions
 Malfunction of transmission between optional controllers for centralized control and indoor unit
Supposed
 Connector for setting master controller is disconnected.
Causes
 Failure of P.C.B. for centralized remote controller
 Defect of indoor unit P.C.B.