Troubleshooting by Indication on the Remote Controller
U0
3.35 "
" Outdoor Unit: Low Pressure Drop Due to
Refrigerant Shortage or Electronic Expansion Valve
Failure
U0
Remote
Controller
Display
Applicable
RZQ18~30PVJU
Models
Method of
Short of gas malfunction is detected by discharge pipe temperature thermistor and low pressure
Malfunction
saturation temperature.
Detection
Malfunction
Microcomputer judge and detect if the system is short of refrigerant.
Malfunction is not decided while the unit operation is continued.
Decision
Conditions
Out of gas or refrigerant system clogging (incorrect piping)
Supposed
Defect of pressure sensor
Causes
Defect of outdoor unit P.C.B. (A1P)
Defect of thermistor R3T