Daikin BRC1C71 Engineering Data page 55

Controls vrv
Table of Contents

Advertisement

Control Devices
4. Install the Upper Part of the Remote Controller as before.
2.6.5 Error Diagnosing Function
This schedule timer is provided with the malfunction-diagnosing function. The malfunction code flashes if there are any
communication malfunctions between the optional controllers for centralized control. In addition, the operation lamp
also flashes if there are any malfunctions with the indoor unit. Check the display and contact your DAIKIN dealer to
report the trouble area indicated.
Operation
Lamp
Turn Off
Turn On or Off
Turn On or Off
Turn On or Off
Flash
Flash
54
Malfunction Code
M1
Failure of PC board of schedule timer
M8
Malfunction of transmission between each optional controller
MA
Improper combination of optional controllers
MC
Address failure of schedule timer
UE
Malfunction of transmission between indoor unit and optional controllers
Malfunction in indoor unit: Refer to the malfunction codes of the indoor remote
controller, and read the accompanying CAUTION FOR SERVICING manual.