Daikin BRC1C71 Engineering Data page 32

Controls vrv
Table of Contents

Advertisement

EDUS39-605
Cautions
Even in the systems without remote control, connect the remote controller once to set the Group Number for
addressing the central control equipment and after it is set, remove the remote controller.
When you set the group No., be sure to supply power to the central remote controller, the unified ON/OFF controller,
and the indoor unit.
Example of group setting
Cautions
When the power is supplied, all the displays appear at once on the remote controller and then the display changes to [88]
for about one minute during which time the remote controller does not function. This is not a malfunction of the remote
controller.
Control Mode Setting(Field Setting)
The control mode defines the function of local remote controllers to handle various types of control and applications.
Functions can be defined by conditions and combinations of local remote control operations such as ON/OFF, etc. See
table on following page.
Operation can always be conducted from the central remote controller except when connected to the central monitoring
panel.
Description of Control Mode
The following 5 operation control modes and 20 temperature/operation combination modes are set with the remote
controller and are displayed by the control mode 0 through 19.
Remote Control Rejection
Choose when you want to turn on/off using only the central remote controller as on/off cannot be conducted by remote
controller.)
Remote controller Off Only Accepted
Choose when you want to turn on only by the central remote controller, and turn off only by local remote controller.
Central Priority
Choose when you want to turn on only by the central remote controller and, during the set time, turn on/off freely by local
remote controller.
Individual Priority (Last Command Priority)
Choose when you want to turn on/off by both central remote controller and local remote controller.
Remote Controller Permission Timer
Choose when you want to turn on/off by local remote controller during set time, but you do not want to start operation
from the central remote controller at the programmed time of system start.
Note:
The control mode consists of numbers 0 through 19, but only 0 through 9 are usually set.
Controls
Control Devices
31