Daikin BRC1C71 Engineering Data page 46

Controls vrv
Table of Contents

Advertisement

EDUS39-605
2. Switch for Setting Each Address (DS1)
The following switches are used to set group control address:
Group Numbers 1-00 through 1-15 are in the same control group when the unit is shipped from the factory.
After setting, attach the number seal applicable to respective control range of the attached switch display sticker, as
shown in the diagram below.
Example:
In The Case of 1-00 to 1-15, Attach N.
3. MAIN/SUB Changeover Switch Setting
With two unified ON/OFF controllers, centralized control for indoor units is possible from different locations. In this
kind of setup, it is necessary to set the MAIN/SUB changeover switch.
One of the two unified ON/OFF controllers (1) is set to MAIN while the other (2) is set to SUB.
4. Setting of the Sequential Operation Function
The unified ON/OFF controller is equipped with a sequential operation function that sequentially turns indoor units on
in 2-second intervals during unified operation. Sequential operation is factory set to ON. To switch sequential
operation ON or OFF, set as shown in the following diagram:
Note:
The sequential operation function is designed to reduce the load on the power supply equipment, but does not guarantee
that compressors will not be started simultaneously. You cannot count on a capacity reduction when selecting equipment
breakers.
Controls
Control Devices
45