Anti-Icing Function In Other Rooms / Unspecified Voltage (Between Indoor And Outdoor Units) - Daikin CTXS09GVJU Service Manual

Super multi nx g-series
Hide thumbs Also See for CTXS09GVJU:
Table of Contents

Advertisement

SiUS12-814
5.28 Anti-icing Function in Other Rooms / Unspecified Voltage
(between Indoor and Outdoor Units)
UA, UH
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
A wrong connection is detected by checking the combination of indoor and outdoor units on the
Malfunction
microcomputer.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Service Diagnosis
1
1
2
1
3
1
4
1
Operation halt due to the anti-icing function in other rooms
Operation halt due to unspecified internal and/or external voltages
Operation halt due to mismatching of indoor and outdoor units
Operation halt due to the anti-icing function in other rooms
Wrong connections at the indoor unit
PCB wrongly connected
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Error-displaying air-
conditioner running?
YES
Supply voltage as
specified?
YES
Check the model number.
Normal?
YES
Check the combination of all the
models being connected.
NO
NO
NO
Troubleshooting
The anti-icing function is
activated in other rooms.
Refer to A5.
Correct.
Reconnect.
(R7151)