Dc Fan Lock - Daikin CTXS09GVJU Service Manual

Super multi nx g-series
Hide thumbs Also See for CTXS09GVJU:
Table of Contents

Advertisement

Troubleshooting

5.13 DC Fan Lock

E7
Remote
Controller
Display
Outdoor Unit LED
A
5
Display
Method of
A fan motor line error is detected by checking the high-voltage fan motor rpm being detected by the
Malfunction
Hall IC.
Detection
Malfunction
Decision
Conditions
Supposed
Causes
Troubleshooting
Check No.15
Refer to P.166
130
1
4
2
4
3
4
4
4
The fan does not start in 30 seconds even when the fan motor is running.
The system will shut down if the error occurs 16 times.
Clearing condition: Continuous run for about 5 minutes (normal)
Fan motor breakdown
Harness or connector disconnected between fan motor and PCB or in poor contact
Foreign matters stuck in the fan
Be sure to turn off power switch before connect or disconnect connector,
Caution
or parts damage may be occurred.
Fan motor connector
disconnected?
NO
Foreign matters in or
around the fan?
NO
Get started.
Check No. 15
Check the outdoor unit PCB rpm
pulse input.
Pulse signal inputted?
YES
YES
YES
NO
SiUS12-814
Turn off the power and
reconnect the connector.
Remove.
Replace the outdoor unit fan
motor.
Replace the outdoor unit
PCB.
(R7139)
Service Diagnosis

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents